Section 3: Screen Descriptions
WCC II Operator’s Guide
Operator Interfaces
3-152
There is one TUC-VR set-up screen for each TUC-VR. To access
this screen, place the cursor above “Velocity Reset” on the Main
Menu and press <Enter>.
Satellite # 4
The satellite number you want to communicate with is entered
here. The SAT II-B is seen as 4 satellite controllers through the
ECC/WCC II Screens.
For example, if you have a SAT II-B addressed #4, it will be seen
as satellite controllers # 4, 5, 6, and 7 on the ECC/WCC II System
Screens. The following table shows how the TUC-VR’s will
appear to the ECC/WCC II. TUC-VR’s 1-8 will be seen through
the screens for satellite #4, TUC-VR’s 9-16 will be seen through
the screens for satellite controller #5, TUC-VR’s 17-24 will be
seen through the screens for satellite #6, and TUC-VR’s 25-32 will
be seen through the screens for satellite controller #7.
TUC-VR SETUP SCREEN
-----------------------------------------------------------------------------------------
Satellite #4 VELOCITY RESET # 1
Mode: [Cooling/electric] Ver.: 01.00
Description: [Rm 100] Temperature Unit: F
Current Status: Local Control when GB 0 is ON
1. Space Temperature: 76 F 2. Setpoint: 74 F
3. Airfl ow: 0 CFM 4. Duct Temperature: 0 F
5. Direct Action 6. Occupied
7. EMS Control 8. Hot Water Valve Position: 0%
Air fl ow rate at 2 in. (50.8 mm) w.g.: [1000 CFM)
Occupied Unoccupied Local Set
Maximum airfl ow (EMS set) 60% 50% 60%
Minimum airfl ow (EMS set) 20% 0% 20%
Aux. fan setpoint (Parallel) 30% 30% 30%
Aux. reheat setpoint diff. 4 F 24 F 4 F
Damper forced closed is GB 0 is ON
Damper forced open if GB 0 is ON Status: Normal
Data reg. A: [Current air fl ow]
Data reg. B: [Space temp - temp setpoint]
Data reg. C (AO): [% of maximum air fl ow rate]
The following options are selected on the panel:
1. [Normal operating reheat]
2. [Parallel fan type]
3. [Proportional control only]
4. Throttling range is [3.0] Deg [F]
5. Rotate damper [CCW] on velocity increase
-----------------------------------------------------------------------------------------